ABB ACH580 Series User Manual page 75

E-clipse bypass and packaged drive
Table of Contents

Advertisement

66
Code
1626
1627
1628
1629
1630
Parameters
Name
Resolution
MODE LOCK
1
COST/KWH
0.1 c/kWh
LEARN MODE
1
LEARN TIME
0.1 Hr
START REV
ACH580 E-Clipse bypass and packaged drive user manual
Group 16: System Control
Range
Default
0 = NOT SEL
NOT SEL
1 = AUTO MODE
2 = LOCAL MODE
0.0 - 100.00 c/
7.0 c/kWh
kWh
0 = NOT SEL
NOT SEL
1 = ENABLED
0.0 - 200.0 Hr
48.0 Hr
0 = NOT SEL
NOT SEL
1 = DI2
Description
When Mode Lock is AUTO
(0)
MODE, the control panel will not
allow switching to Hand or Off.
When Mode Lock is LOCAL
MODE, the control panel will not
allow switching to Auto.
Cost of energy: cents/kWh
When enabled, bypass learns
(0)
average power consumption
while operating in bypass mode
Time that learn mode will be
active after it is enabled
(0)
DI3
DComm
DComm
DI2
Rev Request
+24V
Selects source for drive start
reverse command for a
constant frequency for wiring
diagram above and
programming below.
Reverse request can only be
selected for DI2 on the
E-Clipse
Drive Param 20.21
(Direction) needs to be set for
REQUEST.
Drive Param 28.22 (Constant
Frequency Sel 1) needs to be
set to DI3.
Drive Param 28.26 (Constant
Frequency 1) needs to be set
for frequency required. Use
positive value.
Drive Param 28.21 bit 1
(Direction enable) set to 1.
When E-Clipse input DI2 is
energized the bypass sets
drive's reverse run request
over the communication link.
The same signal input for
bypass DI2 goes to Drive DI3
and sets constant frequency.
The Reverse request has
priority over normal Run
input, this means that if
both DI1 and DI2 are closed
at the same time motor will
run reverse at the constant
frequency.
Drve
ByPass