ABB ACH580 Series User Manual page 163

E-clipse bypass and packaged drive
Table of Contents

Advertisement

154
The state diagram below describes the start-stop function of
and
STATUS WORD
KEY
l = Param. 0104 CURRENT
f = Param. 0103 OUTPUT FREQ
RFG = Ramp Function Generator
Embedded fieldbus
(SW) bits for the ABB Drives profile.
From any state
Emergency Stop
OFF3 (CW Bit2=0)
OFF3
(SW Bit5=0)
ACTIVE
f=0 / l=0
From any state
OFF1 (CW Bit0=0)
f=0 / l=0
(SW Bit2=0)
(CW Bit6=0)
State
CW = CONTROL WORD
SW = STATUS WORD
Path described in example
*This state transition also occurs if the fault is reset from any other source (e.g. digital input).
ACH580 E-Clipse bypass and packaged drive user manual
From any state
Emergency Off
OFF2 (CW Bit1=0)
OFF2
(SW Bit4=0)
ACTIVE
MAINS OFF
Power ON
A
C D
(CW Bit3=0)
OPERATION
INHIBITED
C D
(CW Bit5=0)
D
CONTROL WORD
From any state
Fault
FAULT
(SW Bit3=1)
(CW Bit7=1)*
SWITCH-ON
(SW Bit6=1)
INHIBITED
(CW Bit0=0)
NOT READY
(SW Bit0=0)
TO SWITCH ON
(CW xxxx xxxx xxxx x110)
READY TO
(SW Bit0=1)
SWITCH ON
(CW xxxx xxxx xxxx x111)
READY TO
(SW Bit1=1)
OPERATE
(CW Bit3=1 and
SW Bit12=1)
OPERATION
(SW Bit2=1)
ENABLED
A
(CW Bit5=1)
RFG: ACCELERATOR
ENABLED
C
(CW Bit6=1)
OPERATING
(SW Bit8=1)
D
(CW)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents