Note: For Present Value Access Types, R = Read-only, W = Writeable,
C = Commandable. Commandable values support priority arrays and relinquish
defaults.
Analog output object instance summary – Drive
The following table summarizes the Analog Output Objects supported:
Mailbox Parameter
Mailbox Data
Mailbox Read
Mailbox Write
Note: For Present Value Access Types, R = Read-only, W = Writeable,
C = Commandable. Commandable values support priority arrays and relinquish
defaults.
Embedded fieldbus
Name
Enter the number of the drive group and parameter number
using the format: (group #) * 256 + parameter #.
Example: drive parameter 28.01 is entered as (28 * 256)
+ 1 = 7169
Contains the parameter value after a read, or enter the
desired parameter value for a write.
A binary value triggers a read – the value of the "Mailbox
Parameter" appears in "Mailbox data".
A binary value triggers a write – the drive value for the
"Mailbox Parameter" changes to the value in "Mailbox data".
ACH580 E-Clipse bypass and packaged drive user manual
Description
BACnet
Access Point
AV25
AV26
BV15
BV16