106
N2 binary output objects – Drive
The following table lists the N2 Binary Output objects defined for the ACH580 drive.
Number
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
BO11
BO12
BO13
BO14
BO15
BO16
BO17
BO18
BO19
BO20
1) N2 LOCAL CTL and N2 LOCAL REF have priority over drive input terminals. Use these binary
outputs for temporary N2 control of the drive when
Embedded fieldbus
ACH580 E-Clipse bypass and packaged drive user manual
Object
STOP/START
FORWARD/REVERSE
PANEL LOCK
RUN PERMISSIVE
REF1/REF2 SELECT
FAULT RESET
COMMAND RO 1
COMMAND RO 2
COMMAND RO 3
COMMAND RO 4
COMMAND RO 5
COMMAND RO 6
RESET RUN TIME
RESET KWH COUNT
PRC PID SELECT
N2 LOCAL CTL (Note 1)
N2 LOCAL REF (Note 1)
SAVE PARAMETERS
READ MB
WRITE MB
N2 Binary Outputs:
Drive Parameter
Command Word
0 = Stop, 1 = Start to Speed
Command Word
0 = Forward, 1 = Reverse
Command Word
0 = Open, 1 = Locked
Command Word
0 = Enable, 1 = Disable
Command Word
0 = Ref1, 1 = Ref2
Command Word
Change 0 -> 1 Resets
10.99, bit0
0 = Off, 1 = On
10.99, bit1
0 = Off, 1 = On
10.99, bit2
0 = Off, 1 = On
10.99, bit3
0 = Off, 1 = On
10.99, bit4
0 = Off, 1 = On
10.99, bit5
0 = Off, 1 = On
Indirectly mapping
0 = N/A, 1 = On (Reset Run Time)
Indirectly mapping
0 = N/A, 1 = On (Reset kWh Count)
40.57 (indirectly)
0 = SET2, 1 = SET2
DCU Control Word,
0 = Auto, 1 = N2
BIT16
DCU Control Word,
0 = Auto, 1 = N2
BIT17
96.07 (indirectly)
0 = N/A, 1 = On (Save Parameters)
N/A
0 = NO, 1 = READ
N/A
0 = NO, 1 = WRITE
is not the selected control source.