ABB ACH580 Series User Manual page 113

E-clipse bypass and packaged drive
Table of Contents

Advertisement

104
Number
AI14
AI15
AI16
AI17
AI18
AI19
AI20
AI21
AI22
AI23
AI24
1) Rated Speed Is A Percent Of Maximum Frequency (Parameter 2008) If The Drive Is In Scalar
Mode, And Is A Percent Of Maximum Speed (Parameter 2002) In Speed Mode.
N2 binary input objects – Drive
The following table lists the N2 Binary Input objects defined for the ACH580 drive.
Number
BI1
BI2
BI3
BI4
BI5
BI6
BI7
BI8
BI9
BI10
BI11
BI12
BI13
BI14
BI15
BI16
BI17
BI18
BI20
BI21
Embedded fieldbus
ACH580 E-Clipse bypass and packaged drive user manual
Object
PRC PID DEVIATION
EXT PID FEEDBACK
EXT PID DEVIATION
LAST FAULT
PREV FAULT
OLDEST FAULT
AI 1 ACTUAL
AI 2 ACTUAL
AO 1 ACTUAL
AO 2 ACTUAL
MOTOR TEMP
Object
STOP/RUN
FORWARD/REVERSE
FAULT STATUS
RELAY 1 STATUS
RELAY 2 STATUS
RELAY 3 STATUS
RELAY 4 STATUS
RELAY 5 STATUS
DIGITAL OUT 1 STATUS
INPUT 1 STATUS
INPUT 2 STATUS
INPUT 3 STATUS
INPUT 4 STATUS
INPUT 5 STATUS
INPUT 6 STATUS
EXTERNAL 2 SELECT
HAND/AUTO
WARNING
DRIVE READY
AT SETPOINT
N2 Analog Inputs:
Drive
Resolution
Parameter
40.99
0.1
Derived value
0.1
Derived value
0.1
Derived value
1
Derived value
1
Derived value
1
12.101
0.1
12.102
0.1
13.11
0.1
13.21
0.1
Derived value
1
N2 Binary Inputs:
Drive Parameter
Status Word, BIT2
Status Word, BIT11
Status Word, BIT15
10.21, BIT0
10.21, BIT1
10.21, BIT2
15.04, BIT0
15.04, BIT1
15.04, BIT5
10.02, BIT0
10.02, BIT1
10.02, BIT2
10.02, BIT3
0119 (bit mask 02)
10.02, BIT5
DCU status word, BIT14 0 = EXT1 = EXT2
DCU status word, BIT12 0 = AUTO, 1 = HAND
DCU status word, BIT16 0 = OK, 1 = WARNING
DCU status word, BIT0
DCU status word, BIT7
Units
Range
%
0...100
%
0...100
%
0...100
fault code
fault code
fault code
%
0...100
%
0...100
mA
0...20
mA
0...20
°
C
0...200
Range
0 = Stop, 1 = Drive Running
0 = Forward, 1 = Reverse
0 = OK, 1 = Drive Fault
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Not Ready, 1 = Ready
0 = No, 1 = At Setpoint

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents