ACH580 E-Clipse bypass and packaged drive user manual
• Change of State (COS) enabled
• Warning Enabled
• Warning Enabled
• Override value is received, but there is no action taken.
Binary Input – The binary input objects support the following features:
• Binary Input actual value
• Normal / Warning state specification
• Warning Enabled
• Change of State (COS) enabled
• Override value is received, but there is no action taken.
Analog Output – The analog output objects support the following features:
• Analog Output value in engineering units
• Override value is used to change the Analog Output value. It is not possible to
return to the previous value by removing the override. The override feature is
used only to change the value.
Binary Output – The binary output objects support the following features:
• Binary Output value
• Override value is used to change the Binary Output value. It is not possible to
return to the previous value by removing the override. The override feature is
used only to change the value.
N2 analog input objects – Drive
The following table lists the N2 Analog Input objects defined for the ACH580 drive.
Number
AI1
AI2
AI3
AI4
AI5
AI6
AI7
AI8
AI9
AI10
AI11
AI12
AI13
Object
OUTPUT FREQUENCY
RATED SPEED
SPEED
CURRENT
TORQUE
POWER
DRIVE TEMPERATURE
KILOWATT HOURS
MEGAWATT HOURS
RUN TIME
DC BUS VOLTAGE
OUTPUT VOLTAGE
PRC PID FEEDBACK
N2 Analog Inputs:
Drive
Resolution
Parameter
01.06
0.1
01.62
0.1
01.01
1
01.07
0.1
01.10
0.1
01.17
0.1
05.11
0.1
01.58
1
Derived value
1
05.03
1
01.11
1
01.13
1
40.97
0.1
103
Units
Range
Hz
0...250
%
0...100
rpm
0...9999
A
0...9999
%
-200...200
kW
0...65535
%
-40...160
kWh
0...65535
MWh
0...65535
H
0...65535
V
0...999
V
0...999
%
0...100
Embedded fieldbus