Embedded fieldbus
ACH580 E-Clipse bypass and packaged drive user manual
Object Name
EXT PID DEV
This object is the External PID output
signal's deviation from its setpoint.
Calculated as (drive parameter 71.04) /
drive parameter 71.14).
RUN TIME (R)
This object indicates, in hours, the drive's
accumulated run time since the last reset.
The value can be reset to zero. The
corresponding drive parameter is 05.03.
MOTOR TEMP
This object indicates the drive's motor
temperature, as set up in parameter
Group 35. The corresponding drive
parameter is 35.02 or 35.03 if either
enabled or 35.01.
INPUT REF 1
This object sets 03.09. Group 22 must be
configured to make use of EFB ref 1.
INPUT REF 2
• This object sets 03.10. Group 22 must
be configured to make use of EFB
ref 2.
LAST FLT
This object indicates the most recent fault
entered in the drive's fault log.
PREV FLT 1
This object indicates the second most
recent fault entered in the drive's fault
log.
PREV FLT 2
This object indicates the third most recent
fault entered in the drive's fault log.
AO 1 ACT
This object indicates Analog Output 1's
level. The corresponding drive parameter
is 12.11. Units depend on drive
parameter 12.15.
AO 2 ACT
This object indicates Analog Output 2's
level. The corresponding drive parameter
is 12.22. Units depend on drive
parameter 12.25.
ACCEL1 TIME
This object sets the Ramp1 acceleration
time. The corresponding drive parameter
is 28.72 if 99.04 value = Scalar; 23.12 if
99.04 value = Vector.
DECEL1 TIME
This object sets the Ramp1 deceleration
time. The corresponding drive parameter
is 28.73 if 99.04 value = Scalar; 23.13 if
99.04 value = Vector.
MBOX PARAM
This object defines the parameter to be
read or written to by the mailbox function.
See BV15 and BV16.
MBOX DATA
This object holds the mailbox function's
parameter value – a value that was read,
or is to be written. See BV15 and BV16.
FRQ OUT MIN
This object indicates the drive's minimum
output frequency.
FRQ OUT MAX
This object indicates the drive's
maximum output frequency.
Description
Present Value
Units
Access Type
Percent
R
Hours
W
°C
R
Percent
C
Percent
C
None
R
None
R
None
R
mA or V
R
mA or V
R
Seconds
W
Seconds
W
None
W
None
W
Amps
R
Percent
R