EFB Ref1/Ref2
Drive Parameter
19.11 Ext1/Ext2 Selection
3.09 EFB Ref1
3.10 EFB Ref2
Drive relay output control
Using the fieldbus for relay output control requires:
• Drive parameter values set as defined below.
• Only make these drive programming changes if you require control via BACnet.
• Fieldbus controller supplied, binary coded, relay command(s) in the appropriate
location.
10.24 RO1
Source
10.27
10.30
15.07
15.10
15.23
DO1 Source
1) More than 3 relays requires the addition of a relay extension module.
Analog output control
Using the fieldbus for analog output control requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied analog value(s) in the appropriate location.
13.12
13.91
13.22
13.92
Embedded fieldbus
Drive Parameter
RELAY OUTPUT 1 62, RO/DIO control
RELAY OUTPUT 2 62, RO/DIO control
RELAY OUTPUT 3 62, RO/DIO control
1)
RELAY OUTPUT 4 62, RO/DIO control
1)
RELAY OUTPUT 5 62, RO/DIO control
1)
DIGITAL OUTPUT
1
Drive Parameter
AO1 Source
AO1 Data Storage
AO2 Content Sel
AO2 Data Storage
ACH580 E-Clipse bypass and packaged drive user manual
BACnet Access Point
BV13
AV16
AV17
Value
word
word
word
word
word
62, RO/DIO control
word
Value
37, AO1 Data
Analog Output 1 controlled by
Storage
writing to parameter 13.91.
38, AO2 Data
Analog Output 2 controlled by
Storage
writing to parameter 13.92.
Setting
Access Point
Relay Output 1
BO0
controlled by fieldbus.
Relay Output 2
BO1
controlled by fieldbus.
Relay Output 3
BO2
controlled by fieldbus.
Relay Output 4
BO3
controlled by fieldbus.
Relay Output 5
BO4
controlled by fieldbus.
Digital Output 1
BO5
controlled by fieldbus.
Setting
BACnet
BACnet
Access
Point
AO0
AO1