ABB ACH580 Series User Manual page 161

E-clipse bypass and packaged drive
Table of Contents

Advertisement

152
Bit
10
11
12
13
14
15
Bit
16
17
18
19
20
21...25
26
27
28
29
30
31
Embedded fieldbus
ACH580 E-Clipse bypass and packaged drive user manual
DCU Profile STATUS WORD
Name
Value
REV_REF
1
0
REV_ACT
1
0
PANEL_LOCAL
1
0
FIELDBUS_LOCAL 1
0
EXT2_ACT
1
0
FAULT
1
0
DCU Profile STATUS WORD
Name
Value
WARNING
1
0
REQ_MAINT
1
0
DIRLOCK
1
0
LOCALLOCK
1
0
CTL_MODE
1
0
REQ_CTL
1
0
REQ_REF1
1
0
REQ_REF2
1
0
REQ_REF2EXT
1
0
ACK_STARTINH
1
0
ACK_OFF_ILCK
1
0
Reference is in reverse direction.
Reference is in forward direction.
System is running in reverse direction.
System is running in forward direction.
Control is in control panel (or PC tool) local mode.
Control is not in control panel local mode.
Control is in fieldbus local mode (steals control panel local).
Control is not in fieldbus local mode.
Control is in EXT2 mode.
Control is in EXT1 mode.
Drive is in a fault state.
Drive is not in a fault state.
An warning is on.
No warnings are on.
A maintenance request is pending.
No maintenance request is pending.
Direction lock is ON. (Direction change is locked out.)
Direction lock is OFF.
Local mode lock is ON. (Local mode is locked out.)
Local mode lock is OFF.
Drive is in vector control mode.
Drive is in scalar control mode.
Reserved
Copy the control word
(no op)
Reference 1 requested in this channel.
Reference 1 is not requested in this channel.
Reference 2 requested in this channel.
Reference 2 is not requested in this channel.
External PID reference 2 requested in this channel.
External PID reference 2 is not requested in this channel.
A start inhibit from this channel is granted.
A start inhibit from this channel is not granted.
Start inhibit due to OFF button
Normal operation
Status
Status