ACH580 E-Clipse bypass and packaged drive user manual
Bit
10
11
12
13... 15 Unused
DCU profile
The following tables describe the STATUS WORD content for the DCU profile.
Bit
0
1
2
3
4
5
6
7
8
9
ABB Drives Profile (EFB) STATUS WORD
Name
ABOVE_LIMIT
1
0
EXT CTRL LOC
1
0
EXT RUN
1
PERMISSIVE
0
DCU Profile STATUS WORD
Name
Value
READY
1
0
ENABLED
1
0
STARTED
1
0
RUNNING
1
0
ZERO_SPEED
1
0
ACCELERATE
1
0
DECELERATE
1
0
AT_SETPOINT
1
0
LIMIT
1
0
SUPERVISION
1
0
Value
(Correspond to states/boxes in the state diagram)
Supervised parameter's value > supervision high limit.
Bit remains "1" until supervised parameter's value <
supervision low limit.
See group 32, Supervision
Supervised parameter's value < supervision low limit.
Bit remains "0" until supervised parameter's value >
supervision high limit.
See group 32, Supervision
External control location 2 (EXT2) selected
External control location 1 (EXT1) selected
External Run Permissive signal received
No External Run Permissive signal received
System is ready to receive start command.
System is not ready.
External run permissive signal received.
No external run permissive signal received.
System has received start command.
System has not received start command.
System is modulating.
System is not modulating.
System is at zero speed.
System has not reached zero speed.
System is accelerating.
System is not accelerating.
System is decelerating.
System is not decelerating.
System is at setpoint.
System has not reached setpoint.
Operation is limited by Group 30 settings.
Operation is within Group 30 settings.
Actual value (speed, frequency or torque) is above a
limit. Limit is set with drive parameters 46.31...46.
Actual value (speed, frequency or torque) is within limits.
Description
Status
Embedded fieldbus
151