92
Miscellaneous system control
Note: Control of system commands is dependent upon the setting of bypass
parameter 1625.
Using the fieldbus miscellaneous system control requires:
• Bypass parameter values set as defined below.
• Fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
Bypass Parameter
1602
1603
1604
1605
1606
1607
1625
Embedded fieldbus
Value
RUN
2 (COMM)
PERMISSIVE
(Not
Recommended)
START
2 (COMM)
INTERLOCK 1
(Not
Recommended)
START
2 (COMM)
INTERLOCK 2
(Not
Recommended)
START
2 (COMM)
INTERLOCK 3
(Not
Recommended)
START
2 (COMM)
INTERLOCK 4
(Not
Recommended)
RESET SRC
2 (COMM)
COMM CTRL
1 (SYSTEM)
ACH580 E-Clipse bypass and packaged drive user manual
Setting
Run permissive by
fieldbus.
Source for Start
Interlock 1 is the
fieldbus
Command word.
Source for Start
Interlock 2 is the
fieldbus
Command word.
Fault reset by
fieldbus
Enable System
Control.
Protocol Reference
Modbus
N2
BACnet
400001 bit 2
BO2
BV12
400001 bit 4
BO10
BV15
400001 bit 5
BO11
BV16
400001 bit 6
BO12
BV17
400001 bit 7
BO13
BV18
400001 bit 1
BO3
BV14
N/A