CSBO "BO13",Y,Y,"RST_RTIM","OFF","RESET"
CSBO "BO14",Y,Y,"RST_KWH","OFF","RESET"
CSBO "BO15",Y,Y,"PID_SEL","SET1","SET2"
CSBO "BO16",Y,Y,"N2_LOC_C","AUTO","N2"
CSBO "BO17",Y,Y,"N2_LOC_R","AUTO","N2"
CSBO "BO18",Y,Y,"SAV_PRMS","OFF","SAVE"
CSBO "BO19",Y,Y,"READ_MB","NO","READ"
CSBO "BO20",Y,Y,"WRITE_MB","NO","WRITE"
Bypass overview
The ABB E-Clipse bypass does not support N2 Fieldbus communication "internal
values".
All of the Binary I/O objects are listed below.
Binary Input – The binary input objects support the following features:
• Binary Input actual value
• Normal / Warning state specification
• Warning Enabled
• Change of State (COS) enabled
• Override value is received, but there is no action taken.
Binary Output – The binary output objects support the following features:
• Binary Output value
• Override value is used to change the Binary Output value. It is not possible to
return to the previous value by removing the override. The override feature is
used only to change the value.
N2 analog input objects – Bypass
The following table lists the N2 Analog Input objects defined for the ABB E-Clipse
bypass.
Number
AI1
AI2
AI3
AI4
AI5
AI6
Bypass
Object
Parameter
CURRENT
0101
LAST FAULT
0401
WARNING WORD 1
0308
WARNING WORD 2
0309
HAND OFF AUTO
INPUT VOLT
0102
N2 Analog Inputs:
Resolution
Units
0.1
A
1
1
1
1
V
109
Range
0...9999
fault code
Warning mask (see bypass
manual description of
parameter 0308)
Warning mask (see bypass
manual description of
parameter 0309)
0=Off, 1=Hand, 2=Auto
Average of line-line input
voltage
Embedded fieldbus