ABB ACH580 Series User Manual page 177

E-clipse bypass and packaged drive
Table of Contents

Advertisement

168
Drive relay output control
Using the fieldbus for relay output control requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied, binary coded, relay command(s) in the appropriate
location. (The location is defined by the Protocol Reference, which is protocol
dependent.)
10.24
RO1
Source
10.27
10.30
15.07
15.10
15.23
DO1
Source
1) More than 3 relays requires the addition of a relay extension module.
Note: Relay status feedback occurs without configuration as defined below.
10.21 RO Status
15.04 RO/DO Status
Fieldbus adapter
Drive Parameter
Relay Output 1
Relay Output 2
Relay Output 3
62, RO/DIO
control
1
Relay Output 4
word
1
Relay Output 5
1
Digital Output 1
Drive Parameter
RO 1-3 STATUS
RO 4-6 STATUS
ACH580 E-Clipse bypass and packaged drive user manual
Value
Description
Relay Output 1
controlled by fieldbus.
Relay Output 2
controlled by fieldbus.
Relay Output 3
controlled by fieldbus.
Relay Output 4
controlled by fieldbus.
Relay Output 5
controlled by fieldbus.
Digital Output 1
controlled by fieldbus.
Value
Relay 1...3 status.
Relay 4...6 status.
Protocol Reference
Modbus TCP
ABB DRV
DCU PROFILE
402659 bit 0 or 00033
402659 bit 1 or 00034
402659 bit 2 or 00035
402659 bit 3 or 00036
402659 bit 4 or 00037
402659 bit 8 or 00038
Protocol Reference
Modbus TCP
ABB DRV
DCU PROFILE
402581 or 00033...35
403844 or 00036...37