ABB ACH580 Series User Manual page 77

E-clipse bypass and packaged drive
Table of Contents

Advertisement

68
Note: For wiring requirements and additional configuration detail refer to
Override Mode (Override 2)
Group 30: Fault Function
Code
3001
3002
3003
3004
3005
3006
3007
Group 32: Supervisory Control
Code
3201
3202
3203
3204
3205
3206
Group 33: Information
Code
3301
3302
3303
3304
3305
Parameters
on page 37.
Name
Resolution
UL ACTION
1
UL TIME
1 sec
UL TRIP %
1%
COMM LOSS
1
COMM TIME
0.1s
PHASE LOSS
1
PHASE SEQ
1
Name
Resolution
SUPER CTRL
1
START LVL
1%
STOP LEVEL
1%
START DLY
1s
STOP DLY
1s
FBK LOSS
1
Name
Resolution
FW VERSION
hex
PT VERSION
hex
LP VERSION
CB VERSION
TEST DATE
ACH580 E-Clipse bypass and packaged drive user manual
Group 30: Fault Function
Range
0 = NOT SEL
NOT SEL
1 = FAULT
2 = WARNING
10 - 400 sec
0 - 100%
0 = NOT SEL
NOT SEL
1 = FAULT
2 = CONST SP7
3 = LAST SPEED
0.0 - 600.0s
0 = DISABLE
1 = ENABLE
0 = DISABLE
1 = ENABLE
Group 32: Supervisory Control
Range
Default
0 = DISABLE
DISABLE
1 = ENABLE
0 - 100%
0 - 100%
20 - 3600s
20 - 3600s
0 = BYP STOP
BYP START
1 = BYP START
Group 33: Information
Range
Default
Default
Description
Selects action to be taken if
(0)
underload occurs.
20 sec
Time below underload level
before fault is declared.
20%
Sets power level at which
underload is declared.
This parameter serves similar
(0)
purpose as parameter 58.14 in
drive which specifies behavior if
communication link goes down.
0
Sets the communication fault
time used with COMM LOSS
parameter. A value of "0"
disables the timer.
1
Provides input phase loss
detection for bypass mode.
1
Indicates if drive and bypass
would run the motor in the same
direction.
Description
Enable supervisory control in
(0)
bypass mode.
70%
Value of drive's AI2 that causes
bypass contactor closure.
Applies only in supervisory mode.
30%
Value of drive's AI2 that causes
bypass contactor opening.
Applies only in supervisory mode.
40s
Time that close condition must be
present before contactor is closed.
Applies only in supervisory mode.
60s
Time that open condition must be
present before contactor is
opened.
Applies only in supervisory mode.
Bypass contactor operation if drive
(1)
link fault, drive AI2 loss or
excessive cycling.
Description
Revision of main application
firmware.
Revision of panel text file.
Loading package version.
Control board version.
Advanced