MODBUS addressing – Bypass
0xxxx Registers
MODBUS addressing of 0xxxx registers maps the Bypass Control Word shown in
the following table to the first 16 coils when using the bypass device ID. The coil
number is the bit number plus 1. In other words, bits 0-31 are mapped to 1-32.
Relay output control is possible on the bypass by using coils 33-37 and the bypass
device ID. Relay control on the drive is described in the 0xxxx mapping subsection of
the
Modbus addressing
These registers are summarized in the following tables. Reminder: stop and enable
related bits are valid at only one device subject to the status of bypass
parameter 1625, COMM CTRL.
MODBUS Ref.
00001
00002
00003
00004
00005
00006
00007
00008
00009
00010
00011
00012
00013
00014
00015
00016
00017
00018
00019
00020
00021...00032
00033
00034
00035
00036
00037
00038
Embedded fieldbus
ACH580 E-Clipse bypass and packaged drive user manual
section for the drive device ID on page 139.
MODBUS Registers (0xxxx)
Bypass Device ID
Bit
BCU PROFILE
0
START
1
RESET
2
RUN_DISABLE
3
FBLOCAL_CTL
4
START_DISABLE1
5
START_DISABLE2
6
START_DISABLE3
7
START_DISABLE4
8
OVERRIDE
9
LINK_ON
10
N/A
11
N/A
12
N/A
13
N/A
14
N/A
15
N/A
16
N/A
17
N/A
18
N/A
19
N/A
20-31
N/A
Bypass Relay Output 1
Bypass Relay Output 2
Bypass Relay Output 3
Bypass Relay Output 4
Bypass Relay Output 5
N/A