1xxxx Registers – Bypass
MODBUS addressing of 1xxxx registers maps the Bypass Status Word shown in the
following table to the first 16 coils when using the bypass device ID. The coil number
is the bit number plus 1. In other words, bits 0-31 are mapped to 1-32.
Bypass digital input status can be read using registers 33-37 and the bypass device
ID. Digital input status of the drive is described in the 1xxxx mapping subsection of
the
Modbus addressing
These registers are summarized in the following table.
MODBUS Ref.
10001
10002
10003
10004
10005
10006
10007
10008
10009
10010
10011
10012
10013
10014
10015
10016
10017
10018
10019
10020
10021
10022
10023
10024
10025
10026
10027
10028
10029
section for the drive device ID on page 139.
1.1.1 MODBUS Registers (1xxxx)
Bypass Device ID
Bit
0
READY
1
ENABLED
2
STARTED
3
RUNNING
4
FIELDBUS_LOCAL
5
FAULT
6
WARNING
7
Reserved
8
REQ_CTL
9
OVERRIDE
10
POWERED_UP
11
N/A
12
N/A
13
N/A
14
N/A
15
N/A
16
N/A
17
N/A
18
N/A
19
N/A
20
21
22
23
24
25
26
27
28
BCU PROFILE