102
consume two nodes on a N2 fieldbus segment, if both the drive and bypass objects
are being polled by the system.
Drive device type
For the Metasys and Metasys Companion products, the device type for the ACH580
drive is VND.
When bypass parameter 1625 COMM CTL= (0) DRIVE ONLY, drive's N2 objects are
all supported using the drive's device address. The bypass's N2 objects related to
the control word are no longer valid. For further information on the functional
implications of the setting of parameter 1625, see
page 79.
Bypass N2 Objects Not Valid
Number
BO1
BO2
BO3
BO4
B10
B11
B12
B13
When bypass parameter 1625 COMM CTL= (1) SYSTEM, drive's N2 following
objects related to control are no longer available when using the drive's device
address.
Drive N2 Objects Not Valid
Number
BO1
BO2
BO3
Drive Overview
The ACH580 drive does not support N2 Fieldbus communication "internal values".
All of the Analog and Binary I/O objects are listed below.
Analog Input – The analog input objects support the following features:
• Analog Input actual value in engineering units
• Low Warning limit
• Low Warning limit
• High Warning limit
• High Warning limit
• Differential value for the hysteresis of the Alarms and Warnings
Embedded fieldbus
ACH580 E-Clipse bypass and packaged drive user manual
Object
SYSTEM START
SYSTEM DISABLE
SYSTEM RESET
OVERRIDE
START INTERLOCK 1
START INTERLOCK 2
START INTERLOCK 3
START INTERLOCK 4
Object
START/STOP
RUN PERMISSIVE
N2 LOCAL CTL
Communication setup – EFB
Bypass Parmeter
Command Word
Command Word
Command Word
Command Word
Command Word
Command Word
Command Word
Command Word
Bypass Parameter
Command Word
Command Word
Command Word
on