Programming Contact Id, Sia And Sms - Pyronix PCX-256 Programming Manual

Hide thumbs Also See for PCX-256:
Table of Contents

Advertisement

PCX 256 PROGRAMMING MANUAL
key. ARC Details will be displayed. Repeat
the above for any other ARC stations you are
using. Press the
Calls?' will be displayed, press the
Program Digi Channels
Press the
key to check that the Digi
Channels are what the ARC are looking for.
The first Digi Channel will be shown, once you
have checked this is correct, press the
to move to the next.
To change this channel please see page 38 for
the output types. All default values are shown on
page 58. Once you have completed all the Digi
Channels, 'Program Digi Channels will be
displayed'. Press the
'Program SMS Details' will be displayed and
Press the
key.
3 Way Calling
Enter
: for No (Default)
Enter
: for Yes
Press the
key. You will be returned to the
Engineer Menu.

5.23.3 Programming Contact ID, SIA and SMS

The Contact ID, SIA and SMS signalling protocols can also be used. However the programming
differs from Fast Format, here you have to select fixed content types (as opposed to programmable
outputs) you would like to be sent to the ARC. The table below shows all the content types.
Content Types
01
Arm
02
Disarm
03
Special Disarm
04
Arm Fail
05
Alarm
06
First alarm
07
Alarm Silenced
08
Confirmed
09
LoTechFault
10
HiTechFault
11
Tech Info
12
Manager Info
13
Engineer Info
14
AccessC Alarm
15
AccessC Info
16
AccessC Ref
Page: 60
key. 'Program Digi/SMS
key.
key.
All arm events (by area/level & user name)
All disarm events (by area/level & user name)
Disarm events initiated by codes 15 to 20 only
Attempt to arm the system failed
All alarm events (by partition, level and type) inc. code guess (excludes
tampers and emergency input types)
First to alarm event (for each input) only
Any alarm/fault silenced (by partition)
Sequentially confirmed alarm
Telecom Line restore (STU/ATE or DigiModem)
Low volts, Battery fault/OK, Fuse failure, RS-485 or Device Failure
System restart, Over current, Logs cleared
Code changed / deleted
Engineer accessing system, and leaving
Access Control door forced or left open
Access Control tag at Reader
Access refused (invalid code)
key
RINS868-6

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents