Functions, Settings and Wiring
Removing the Cover
Place your thumb at the bottom
left edge of the cover and push
it to the right.
Setting Procedure
1, 2, 3...
4. Follow the setting procedure described below to set the input range for each
input point.
Under the Cover
SW1 (DIP switch to
select input points)
SW2 (toggle switch to
read input range)
1. Remove the cover from the front face of the Unit.
2. The numbers on the DIP switch pins (SW1) indicate the input ports 1 to 8.
Initially, turn ON only pin 1 and make sure that all other pins are OFF.
3. Apply the minimum (offset) value of voltage (0 V) or current (0 mV) to input 1.
The offset converted output is 000
4. Set the toggle switch (SW2) down to read the offset.
SW 1
SW 2
Read offset
5. Apply the maximum (gain) value of voltage (10 V) or current (10 mV) to input
1. The gain converted output is FFF
6. Set the toggle switch (SW2) up to read the gain.
SW 1
SW 2
Read gain
Attaching the Cover
Hold the cover between your thumb
and middle finger, position the lower
edge and push the cover into place
with your index finger.
Press with a pen tip, etc.
.
Hex
Firmly press toggle switch. Toggle
switch automatically resets and returns
to original position when released.
.
Hex
Firmly press toggle switch. Toggle
switch automatically resets and returns
to original position when released.