Specifications And General Information; Specifications; Section 9 C500-Da501 Analog Output Unit - Omron SYSMAC C Series Operation Manual

Analog i/o units
Hide thumbs Also See for SYSMAC C Series:
Table of Contents

Advertisement

Specifications and General Information

9-1

Specifications and General Information

9-1-1 Specifications

General Specifications
Performance Specifications
Item
Number of analog
8
output points
Output signal
Voltage outputs
range
Current outputs
Max. output current Voltage outputs
External output
Voltage outputs
impedance
Max. load
Current outputs
resistance
i
Voltage outputs
Power supply from
5 VDC (supplied from Backplane)
PC
24 VDC ±5%
External power
supply
Resolution
1/4095 (full scale)
Conversion data
Without Scaling
ranges
Voltage outputs
Current outputs
Voltage outputs
With Scaling
Range: Scaling lower limit to scaling upper limit (see note below)
The upper and lower limits must be within the following ranges.
BCD mode: Decimal values –7999 to 7999 (F999 to 7999
Binary mode: Decimal values –32767 to 32767 (8001 to 7FFF
Note:
136
All general specifications of the C500-DA501 Analog Output Unit conform to
those of the C Series, except the following:
Item
Ambient operating
temperature
0 to 10 V
0 to 5 V
–5 to 5 V
–10 to 10 V
0 to 20 mA
4 to 20 mA
10 mA
0.5 Ω max.
750 Ω max.
10 kΩ min.
0 to 10 V
0 to 5 V
0 to 20 mA
4 to 20 mA
–5 to 5 V
–10 to 10 V
The scaling lower limit can be greater than the scaling upper limit, in which case reverse
scaling will be performed.
Specification
8 points with voltage outputs: 0 to 55_C
4 points with voltage or current outputs: 0 to 50_C
8 points with current outputs: 0 to 45_C
Specification
Settable as shown on the left for each output point.
(All 8 output points are factory-set to 0 to 10 V.)
Voltage outputs: The range is set using the DIP switches
on the rear panel and the voltage output range
short-circuit pins on the front panel
short-circuit pins on the front panel.
Current outputs: The range is set using the DIP switches
on the rear panel.
BCD mode: Unsigned decimal values in BCD, 0 to 4095
(0000 to 4095
)
Hex
Binary mode: Unsigned decimal values in binary 0 to
Binary mode: Unsigned decimal values in binary, 0 to
4095 (0000 to 0FFF
)
Hex
(BCD or binary can be set for each output point.)
BCD mode: Signed decimal values in BCD, –2048 to 2047
(A048 to 2047
)
Hex
Binary mode: Signed decimal values in binary, –2048 to
2047 (F800 to 07FF
)
Hex
(BCD or binary can be set for each output point.)
)
Hex
)
Hex