Specifications and General Information

3-1
Specifications and General Information

3-1-1 Specifications

General Specifications
Performance Specifications
PC Write Delay
18
All general specifications of the 3G2A5-AD006 and 3G2A5-AD007 Analog Input
Units conform to those of the C Series, except the following.
• Insulation between the External Terminals and the Frame:
5MΩ min. at 250 VDC
• Breakdown Voltage between the External Terminals and the Frame:
500 VAC, 50-60 Hz for 1 minute
Item
Number of analog inputs
Input signal range
p
g
g
Max. input signal
p
g
External input impedance
p
p
Resolution
PC signal
Linearity error
Accuracy
Accuracy temperature coefficient ±150 PPM/°C (full scale)
Conversion time
Conversion cycle
Max. PC write delay (see note)
Conversion method
Words allocated
External connections
Power consumption
External dimensions
Weight
Note The PC write delay is the time required for a change in the input signal to be con-
verted and transferred to the PC bus.
Analog input signal
Digital output signal
4
Voltage input
g
p
Current input
Voltage input
Current input
Voltage input
Current input
1/1023 (full scale)
10-bit binary
±0.2% max.
±0.2% max. (full scale at 25°C)
2.5 ms max./point
10 ms max.
1 s max.
Sequential comparison
4 input words
17-pin terminal block (not removable)
750 mA max. at 5 VDC
34.5 x 250 x 113 mm (W x H x D)
650 g max.
0
Conversion
cycle
0000
PC write delay
Section 3-1
Specification
AD006 1 to 5 V
AD007 0 to 10 V
AD006 4 to 20 mA
±15 V max.
±60 mA max.
1 MΩ min.
250 Ω
Time
A filter inside the Unit causes
the digital signal to increase
in a stepwise fashion.
Time