7.10.2 Mode Setting

Path:
SETUP
After entering the MODE SETTING screen (shown in figure below), the user can set up
the UPS system mode, of which there are 5 options: On-Line Mode, Green Mode, ECO
Mode, Energy Recycle Mode and Frequency Conversion Mode. These settings must
be performed by qualified service personnel. Please contact Delta customer service for
assistance.

MODE SETTING

Item
On-Line Mode
Green Mode
ECO Mode
Energy Recycle
Mode
Frequency
Conversation
Mode
Modulon DPH Series
UPS-1.1
MEASUREMENT
SETUP
Mode Setting
Select to change system mode
On-Line
Green
Set up the UPS in on-line mode. In on-line mode, it is the inverter to
supply power to the connected loads.
Set up the UPS in green mode. In green mode, it is the inverter to
supply power to the connected loads and the power modules take
turn to rest according to the situation of total load capacity.
Set up the UPS in ECO mode. In ECO mode, it is the bypass to
supply power to the connected loads. It is suggested that you set
the UPS in ECO mode only when there is stable main AC power.
Otherwise, power supply quality will be compromised.
Set up the UPS in energy recycle mode. In energy recycle mode,
the full load output can be simulated for the aging test without real
output to the loads.
Set up the UPS in frequency conversation mode. In frequency
conversation mode, it is the inverter to supply power to the
connected loads with a fixed output frequency. Please note that the
output will be terminated once the inverter is turned off.
MAINTENANCE
LOG IN
EVENT LOG
Administrator
Energy
ECO
Recycle
Description
7-24
10:15
May 25,2018
Bypass
Frequency
Conversion