7.10.3 Output Setting

Path:
SETUP
After entering the OUTPUT SETTING screen (shown in the figure below), the user can set up
the following items. These settings must be carried out by qualified service personnel. Please
contact Delta customer service for assistance.
UPS-1.1

OUTPUT SETTING

Item
Voltage
Frequency
Slew Rate
Power Factor
Power Module
Redundancy
Asynchronous
Transfer Time
Module
Sequential Start
System
Sequential Start
MEASUREMENT
SETUP
MAINTENANCE
Output Setting
Voltage
Frequency
240
V
Power Factor
PM Redundancy
0.0
Module Sequential Start
6
s
Set up the output voltage.
Set up the output frequency as 50Hz (default) or 60Hz. The system
will automatically select the output frequency in accordance with the
bypass power.
Set up the maximum permissible speed for the system output
frequency to catch up the bypass frequency variation.
Set up the output power factor (range: 0.9~1.0).
Set up how many power modules that need to be preserved for
redundancy.
When it is impossible for the inverter to reach synchronous phase
lock with the bypass, the output will be terminated during conversion
process according to this setup time.
Set up the time interval for every power module to be converted
from the battery mode to online mode. The setup is applicable to the
generator to avoid bearing the whole loads right away.
Set up the time interval for the system to be converted from
the battery mode to online mode. The setup is applicable to the
generator to avoid bearing the whole loads right away.
LOG IN
EVENT LOG
Administrator
Slew Rate
60
Hz
0.5
Asnyc Transfer Time
0
1
System Sequential Start
2
s
Description
7-25
7
LCD Display & Settings