4.1.6 Input Dry Contacts

There are four sets of programmable input dry contacts (see Figure 4-10). Please use the
touch panel to set each dry contact as normally open (NO) or normally closed (NC). The
input dry contacts allow the UPS to receive external signals from peripheral devices and let
the UPS response accordingly. Each input dry contact can be assigned with a specific event.
There are four events can be assigned according to your applications. To learn how to set
up, please contact your local dealer and refer to 7.10.6 Dry Contact Setting. For information
about the four events, please refer to the table below.
Modulon DPH Series
I/P DRY
CONTACT
P1
P2
P3
P4
Dry-1
Buffer
Dry-2
Buffer
Dry-3
Buffer
Dry-4
Buffer
(Figure 4-10: Input Dry Contacts Design)
4-10
5V
13
P1
15
2mA. Max
5V
17
P2
19
2mA. Max
5V
14
P3
16
2mA. Max
5V
18
P4
20
2mA. Max
UPS