Eco Mode Start-Up Procedures - Delta Modulon DPH series User Manual

200-500 kva , three phase
Hide thumbs Also See for Modulon DPH series:
Table of Contents

Advertisement

8
UPS-1.1
Power Flow
Power Flow
Summary
System Status

6.2.5 ECO Mode Start-up Procedures

1
Ensure that the manual bypass breaker or switch (Q3) of the Delta or non-Delta external
maintenance bypass cabinet is in the OFF position.
2
Switch ON each external battery cabinet's breaker (Q5).
3
Single Input:
Switch ON the bypass switch (Q0) of the UPS, the input breaker or switch (Q1) and the
output breaker or switch (Q4) of the Delta or non-Delta external maintenance bypass
cabinet.
Dual Input:
Switch ON the bypass switch (Q0) of the UPS, the input breaker or switch (Q1), the
bypass breaker or switch (Q2) and the output breaker or switch (Q4) of the Delta or
non-Delta external maintenance bypass cabinet.
Modulon DPH Series
After selection of 'YES' to start up the inverter, each power module will start up
and perform self-inspection. At the same time, the system begins synchronization
with the bypass AC source. After the self-inspection is completed, the UPS will
automatically transfer to run in online mode, the tri-color LED indicator will illuminate
green and the following screen will appear. For the tri-color LED indicator location,
please refer to Figure 2-11.
MEASUREMENT
SETUP
POWER FLOW
Maintenance
Bypass
Bypass
Mains
90 %
5 mins
(Figure 6-20: Online Mode Screen)
WARNING:
1. For parallel units, please follow 6.2.3 Bypass Mode Start-up Procedures to turn
on each parallel UPS. After confirming that parallel operation can be normally
run, follow the following procedures step by step.
2. For parallel units, ensure that every operation procedure mentioned below is
synchronized to all parallel UPSs.
3. For parallel application, if you just want to operate a specific UPS but not all
parallel ones, please contact service personnel.
MAINTENANCE
LOG IN
EVENT LOG
User
6-18
10:15
May 25,2018
On-Line
Load
30 %

Advertisement

Table of Contents
loading

Table of Contents