Wiring and assembly
5.4 Wiring the ET 200S
Connectable wires
You can connect solid and flexible conductors with PVC insulation with a wire cross-section
between 0.5 mm
conductors is the same they can be wired fifty times. A list of the tested conductors can be
found on the Internet (http://www.idc2.com).
UL-compliant cables and connections
Wiring range for insulating piercing connection 22-16 AWG solid/stranded PVC insulated
conductors, UL style no. 1015 only.
Proceed as follows
1. Insert the unstripped cable in the round opening until it stops (the insulation and
2. Insert the screwdriver into the opening above the slider until it stops.
3. Press the screw driver downwards until the slider reaches the end position.
Note
If you would like to reuse a conductor after it was already connected once then it must be
recut.
82
and 1.5 mm
2
conductor must form a flat surface).
Figure 5-4
Wiring terminal modules with Fast Connect
Result: The wire is connected.
(max. external diameter 3.2 mm). If the cross-section of the
2
Operating Instructions, 08/2008, A5E00515771-06
ET 200S