Commissioning ET 200S on PROFIBUS DP

Software Requirements
The table below details the software requirements for commissioning on PROFIBUS DP.
Table 6- 2
Software requirements for commissioning on PROFIBUS DP
Configuration software
used
STEP 7
Configuration software for
a different DP master used
Requirements for commissioning
The following additional requirements must be satisfied for commissioning the ET 200S on
PROFIBUS DP:
● DP slave installed
● DP slave wired up
● DP slave is configured (configured and parameters assigned)
● Supply voltage for the DP master is switched on (see manual for the DP master)
● DP master is switched to RUN mode (see manual for the DP master)
Proceed as follows
To commission the DP slave, proceed as follows:
1. Switch on the power supply for the DP slave.
2. If necessary, switch on the supply voltage for the load.
See also
Basic principles of configuration for the ET 200S on PROFIBUS DP (Page 102)
Basic principles of installation (Page 51)
Setting the PROFIBUS Address (Page 111)
Wiring rules for the ET 200S (Page 79)
ET 200S
Operating Instructions, 08/2008, A5E00515771-06
Version
from Version 5.0 and
ServicePack 3
You use HW Config. With Service Pack 3 or higher the ET 200S is
included in the hardware catalog.
You need the GSD file from ET 200S.