Wiring and assembly
5.4 Wiring the ET 200S
4. Strip the insulation from the ground wire (from 6 mm to 25 mm
5. Attach the other end to the ground bus.
Note
To stabilize the shield connection, you must mount and screw in at least one shield
terminal above the shield connection element.
86
ground connection terminal (under the conductor rail). Tighten the ground connection
terminal (2 Nm to 2.5 Nm).
5
4
Shield terminal
Insulation material removed
Cable to the encoder
Cable to the ground bus
Ground connection terminal
Figure 5-7
Connecting cable shields