Leakage resistance

C.1

Establishing the leakage resistance of an ET 200S station

Ohmic resistance
When establishing the leakage resistance for an ET 200S station (e.g. for a ground-fault
detector) you must take the ohmic resistance from the RC combination of the relevant
module into account:
Interface module
IM151-1 COMPACT
Power Module PM-E DC24V
PM-E DC24V/AC120/230V power module
Formula
With the following formula you can calculate the leakage resistance of an ET 200S station if
you protect all the aforementioned modules withone ground-fault detector:
R
ET200S
R
ET 200S
R
module
N
R
IM 151
R
IM 151
R
PM-E DC24V
If you protect the modules within an ET 200S station listed above with several ground-fault
detectors, you must determine the leakage resistance for every single ground-fault detector.
ET 200S
Operating Instructions, 08/2008, A5E00515771-06
Module
=
= Leakage resistance of the ET 200S station
= Leakage resistance of a module
= Number of power modules and the interface module in the ET 200S
station
= R
= R
PM-E DC24V
module
= Leakage resistance of the IM151-1 interface module
= Leakage resistance of power module PM-E DC24V
Ohmic resistance from RC network
10 MΩ (±5 %)
10 MΩ (±10 %)
10 MΩ (±5 %)
= 9.5 MΩ