Brief instructions on commissioning ET 200S
2.2 Commissioning on PROFINET IO
Simulating a wire break in the actuator wiring
1. Remove the cable from terminal 1 on the 2DO DC24V/0.5A HF electronic module (slot 7)
2. Monitor the status LEDs:
3. Evaluate diagnostic data record C00A
4. Reattach the cable to the actuator in terminal 1 and reevaluate the diagnostics:
40
IM151-3 PN:
– SF: lights up
Electronic module 2DO DC24V/0.5A HF:
– SF: lights up → there is a diagnostic message
– 1: off → output is not activated
You can find information about evaluating the diagnostic data record C00A
PROFIBUS DP to PROFINET IO
(http://support.automation.siemens.com/WW/view/en/19289930)" programming manual in
the section "Structure of diagnostics data records".
– Status LEDs on the IM151-3 PN:
SF: off
– Status LEDs electronic module 2DO DC24V/0.5 A HF:
SF: off
1: off/on
– The diagnostic message is deleted.
.