Wiring terminal modules for power modules
The terminal assignment of the terminal module depends on which power module is
inserted. You can find information regarding the terminal and power modules in the
device manual.
Wiring terminal modules for digital, analog, and technological modules
The terminal assignment of the terminal module depends on which electronic module is
inserted. You can find information regarding the terminal and electronic modules in the
ET 200S
Technological Functions
Wiring terminal modules for COMPACT modules
The terminal assignment of the terminal module depends on which COMPACT module is
inserted. You can find information regarding the terminal and COMPACT modules in the
chapter entitled
Connecting the Cable Shielding
We recommend that you use the shield connection to connect cable shielding (e.g. in the
case of analog electronic modules, the 1COUNT 24V/100kHz electronic module and the
1SSI electronic module.).
1. Remove the insulation material from the area around the shield terminal, and clamp the
2. Tighten the shield terminal (approximately 0.5 Nm)
3. Repeat steps 1 and 2 if you want to connect additional cable shields.
ET 200S
Operating Instructions, 08/2008, A5E00515771-06
device manual. You can find information about technological modules in the
manual.
COMPACT- Modules
cable shield in the shield terminal (above the conductor rail). The shield clamp is suitable
for one cable with a maximum diameter of 8 mm or two cables with a maximum diameter
of 4 mm each.
ET 200S
and in the
device manual.
Wiring and assembly
5.4 Wiring the ET 200S
ET 200S
85