Evaluating Diagnostic Messages - Siemens SIMATIC ET 200S Operating Instructions Manual

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

2.2.7

Evaluating diagnostic messages

Introduction
In this example, you generate alarms by provoking errors on the ET 200S.
In the event of an error, OB 83 is started. Evaluate the start information in OB 83.
Tip: Call up the SFB 52 within the OB 83 and evaluate the E002
Removing and inserting the 2 DI DC24V HF digital electronic module
1. Remove the 2 DI 24VDC HF electronic module from the terminal module
2. Monitor the status LEDs on the IM 151-3 PN interface module:
3. In the event of a remove interrupt the OB 83 is started. Start the SFB 52 in OB 83.
4. Reinsert the removed electronic module into the terminal module.
ET 200S
Operating Instructions, 08/2008, A5E00515771-06
(e.g., from slot 2) during operation.
– SF: lights up → there is a diagnostic message.
– BF: off
– ON: lights up
Result: The ET 200S continues to run error-free.
Evaluate the E002
diagnostic data record.
H
You can find information about evaluating the diagnostic data record E002
PROFIBUS DP to PROFINET IO
(http://support.automation.siemens.com/WW/view/en/19289930)" programming manual in
the sections "Structure of the configuration data record W#16#E002" and "Blocks of the
diagnostics and configuration records".
Result:
– Status LEDs on the IM151-3 PN interface module:
SF: off
BF: off
ON: lights up
– Once the module is inserted, diagnostic data record E002
discrepancy between the preset and actual configurations for any slot.
Brief instructions on commissioning ET 200S