Brief instructions on commissioning ET 200S
2.1 Commissioning on PROFIBUS DP
Switching off load voltage on the power module
1. Switch off the load voltage on the PM-E DC24V (slot 1).
2. Monitor the status LEDs.
3. Evaluate the diagnostics.
4. Switch on the load voltage back on the power module and re-evaluate the diagnostics.
28
IM151-1 STANDARD:
– SF: lights up
Power module:
– PWR: off → no load voltage available on the power module
– SF: lights up → there is a diagnostic message.
I/O modules in the voltage group:
– LEDs: light up
Result:
– Station status 1 (byte 0): Bit 3 is set → external diagnostics
– ID-related diagnostics: Byte 7.0 is set → slot 1
– Channel-specific diagnostics:
Bytes 35.0 to 35.5: 000000
Bytes 37.0 to 37.4: 10001
Result:
– Status LED on the IM 151-1 STANDARD:
SF: off
– Status LEDs on power module:
PWR: on
SF: off
– Status LEDs on I/O modules:
LEDs: off
– The diagnostic message is deleted.
→ slot 1
B
→ sensor or load voltage missing
B
Operating Instructions, 08/2008, A5E00515771-06
ET 200S