Installing

4.2 Installing the interface module

4.2
Installing the interface module
Introduction
● The interface module connects the ET 200S with the PROFIBUS DP and PROFINET.
● The interface module transfers data between the higher-level controller and the I/O
Requirements
● The DIN rail is installed.
● All terminal modules are installed to the right of the interface module. The maximum
Required tools
Screwdriver with 3 mm blade
Installing the interface module
1. Hang the interface module on the rail.
2. Tip the interface module back until you hear the slider engage.
Removing the interface module
The interface module is wired, and the terminal modules are on the right:
1. Switch off the supply voltage on the interface module.
2. Disconnect the wiring and the bus connector on the interface module.
3. Use a screwdriver to push the slider on the interface module down until the mechanism
4. Press down on the slider while taking the interface module off the mounting rail.
54
modules.
configuration of the ET 200S distributed I/O system is 12/63 I/O modules.
Figure 4-2
Installing the interface module
stops and move the interface module to the left.
Note: The locking mechanism is beneath the interface module.