Commissioning
6.2 Commissioning on PROFIBUS DP
Setting the PROFIBUS DP address
1. Slide the window
2. Use a screwdriver to set the desired PROFIBUS DP address via the DIP switch.
3. Close the window.
Setting the PROFIBUS DP address
You change the PROFIBUS DP address in exactly the same way as you set it. A change in
the PROFIBUS DP address becomes valid for the ET 200S after a POWER ON at the
interface module / COMPACT module.
112
– upwards on the interface module.
– downwards on the COMPACT module.
CAUTION
When open, the window protrudes out from underneath the COMPACT module case.
This can cause it to be easily broken off.
Figure 6-5
Setting the PROFIBUS Address