General technical specifications

8.3 Transport and storage conditions

Emission of Radio Interferences
Emission of interference from electromagnetic fields in compliance with EN 55011: Limit
class A, group 1 (measured at a distance of 10 m).
Frequency
from 30 to 230 MHz
from 230 to 1000 MHz
8.3
Transport and storage conditions
Transport and storage conditions
The ET 200S distributed I/O system surpasses the IEC 61131-2 requirements of transport
and storage conditions. The specifications below apply to modules which are transported
and stored in their original packaging.
Type of condition
Free fall
Temperature
Rate of temperature change
Air pressure
Relative humidity
132
Emitted interference
< 40 dB (µV/m)Q
< 47 dB (µV/m)Q
Permitted range
≤ 1 m
between –40 °C and +70 °C
20 K/h
between 1080 and 660 hPa (corresponds with altitudes of 1000 m to
3500 m)
From 5 % to 95 %, without condensation