Siemens SIMATIC ET 200S Operating Instructions Manual page 134

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

General technical specifications
8.4 Mechanical and Climatic Ambient Conditions
Mechanical ambient conditions
The table below shows the mechanical ambient conditions in the form of sinusoidal
oscillation.
ET 200S modules
All modules except motor starters
Testing for Mechanical Ambient Conditions
The following table provides information about the type and scope of testing for mechanical
ambient conditions.
Testing
Test Standard
Vibrations
Vibration test to
IEC 60068-2-6
Shock
Shock, tested to
IEC 60068-2-27
Repetitive shock
Shock, tested to
IEC 60068-29
134
Frequency range
10 ≤ f ≤ 58 Hz
58 ≤ f ≤ 150 Hz
Terminal modules and electronic modules
Type of vibration: Frequency cycles with a rate of change of 1
octave/minute.
10 Hz ≤ f ≤ 58 Hz, constant amplitude 0.35 mm
58 Hz ≤ f ≤ 150 Hz, constant acceleration 5 g
Duration of vibration: 20 frequency cycles per axis in each of the 3
mutually perpendicular axes
Type of shock: Half-sine
Type of shock: 15 g peak value, 11 ms duration
Direction of shock: 3 shocks each in +/- direction in each of the
3 mutually vertical axes
Type of shock: Half-sine
Type of shock: 25 g peak value, 6 ms duration
Direction of shock: 1000 shocks each in +/- direction in each of the
3 mutually vertical axes
Constant
0.15 mm amplitude
2 g constant acceleration
Operating Instructions, 08/2008, A5E00515771-06
Intermittent
0.35 mm amplitude
5 g constant acceleration
ET 200S