Wiring and assembly
5.4 Wiring the ET 200S
5.4.8

Wiring an interface module with PROFINET IO interface (electrically)

Introduction
Connect the supply voltage and the bus connectors to the IM151-3 PN interface module.
Requirements
● Wire the interface module with the supply voltage switched off.
● Follow the wiring rules.
Note
Provide a suitable strain relief for the PROFINET connecting cable.
Note
Guideline for setting up modules with PROFINET I/O interfaces
You may only operate modules with PROFINET I/O interfaces in LAN networks if all
connected nodes are equipped with SELV/PELV power supplies (or have equivalent
protection).
For linking up to the WAN, a data transfer point is prescribed that guarantees this degree
of safety.
Note
When using a CPU 315-2 PN/DP or CPU 317-2 PN/DP an industrial-quality switch must be
placed directly on the CPU to which the downstream I/O devices must be connected.
Required tools
● Screwdriver with 3 mm blade
● Industrial Ethernet Fast Connect stripping tool (6GK1901-1GA00) (stripping tool for
Required accessories
● PROFINET connector (according to the specifications in the
● Industrial Ethernet Fast Connect installation cables
92
Industrial Ethernet Fast Connect installation cables)
Guide
)
The following are suitable:
Fast Connect standard cable
Fast Connect trailing cable
Fast Connect marine cable
6XV1840-2AH10
6XV1840-3AH10
6XV1840-4AH10
Operating Instructions, 08/2008, A5E00515771-06