Initiating Synchronization Command; Prerequisites; Commanding Synchronization - Honeywell Experion C300 User Manual

Hide thumbs Also See for Experion C300:
Table of Contents

Advertisement

Step
form.
2
On the Main tab, click Controller Command box and select Shutdown from
the list.
3
Click the Yes button to confirm the action.
4
Wait for the C300 Controller to reboot to its RDY state.
5
This completes the procedure.

Initiating Synchronization command

Use the following procedure to initiate a synchronization command manually to a
redundant C300 Controller pair.

Prerequisites

You can view active redundant C300 Controller pair on the Monitoring tab in Control
Builder.

Commanding synchronization

Step
1
In the Monitoring tab, double-click the primary C300 icon to call up its
Parameters configuration form.
2
Click the Redundancy tab to display it.
3
Click the Enable Synchronization button.
4
Click the Yes button to confirm the action and issue the synchronize
command.
5
Confirm that the Auto Synchronization State is, or becomes ENABLED and
confirm that sync cycles in the primary C300 Controller's 4-character display.
6
Click the OK button to close the Parameters form.
7
This completes the procedure.
R301.1
11/06
Experion C300 Controller User's Guide
Honeywell
Initiating Synchronization command
Action
Action
Prerequisites
177