Convert a non-redundant C300 Controller to a redundant controller
To convert a non-redundant C300 Controller to a Redundant controller
Step
3
Add a check to the Module is redundant
check box.
4
Click the OK button.
5
Load the primary C300 block to the
controller.
6
Connect the Redundancy cable between
the redundant controller pairs.
50
Action
Experion C300 Controller User's Guide
Honeywell
Result
A default tag name of the secondary
C300 Controller block appears in the
Secondary Tag Name field. Usually it is
the primary controller block's name with
SEC appended to it.
The C300 Controller configuration form
closes.
In the Project window:
The C300 Controller icon indicates
that it is configured as redundant,
(showing a double controller icon). A
double 'V' sign is shown next to the
primary icon.
An additional C300 Controller icon is
created representing the secondary
controller.
The double 'V' disappears from the
primary C300 icon in the Project view.
The C300 block in the Monitor view
changes from a non-redundant icon to a
redundant icon.
A 'Not Synchronized' alarm may be
generated.