CEEC300 via parameters. The following table summarizes the parameter data you can
monitor and/or configure on the Main tab of the configuration form for the selected
CEEC300 block.
Plain Text
Main
Tag Name
Item Name
Base Execution
Period
Command/State
Control Execution
Environment(CEE)
Command
Control Execution
Environment(CEE)
State
User Lock for CEE
Run
User Lock for CEE
Idle
Program Access may
command CEE from
Idle to Run
R301.1
11/06
Parameter Name
Tag Name
Item Name
BASEPERIOD
CEECOMMAND
CEESTATE
USERLCKTORUN
USERLCKTOIDLE
PROGLCKTORUN
Experion C300 Controller User's Guide
Honeywell
CEEC300 Function Block
User
Configurable
Project Only
System assigned or
user configured unique
name. Consisting of up
to 16 characters and at
least one character
must be a letter (A-Z).
Project Only
A non-unique name by
which an entity is
known within the
context of the enterprise
model.
Yes
Indicates the base
execution period for the
CEE block.
Yes
Indicates the command
to change the
CEESTATE parameter.
No
The current state of
CEE.
Yes
Indicates the user level
required to perform a
coldstart and warmstart.
Yes
Indicates the user level
required to command
CEEIDLE.
Yes
Determines whether
program access is
allowed to command
CEE from Idle to Run.
Main Tab
Notes
107