Configure A Secondary C300 Controller Block - Honeywell Experion C300 User Manual

Hide thumbs Also See for Experion C300:
Table of Contents

Advertisement

Configure a Secondary C300 Controller block

To configure a CEEC300 function block
Step
23
Accept default or click
button to select another value specific to
the given environment. Press <Tab>.
24
Accept the default or key in desired
value. Click Server History tab.
25
Use the on-line help as a guide to
complete the configuratrion entries on
this tab. Click on the Server Displays
tab.
26
Use the on-line help as a guide to
complete the configuratrion entries on
this tab. Click the OK button.
This completes the configuration
procedure for C300CEE block.
REFERENCE - INTERNAL
See the Experion Control Builder Components Reference, Component
Categories and Types and the Experion Planning Guide
Configure a Secondary C300 Controller block
When a C300 Controller is configured as Redundant, the Secondary C300 Controller
block is added to the Project tab automatically.
Prerequisites
Control Builder is running
Tree windows are open
Considerations
All illustrations used in the procedure are for example purposes only.
46
Action
down-arrow
Experion C300 Controller User's Guide
Honeywell
Result
Moves cursor to Store Expiration Time
column.
Calls up the Server History configuration
form.
Calls up the Server Displays
configuration form.
Closes the form.
R301.1
11/06