READY
FAIL
C300 Controller states in application mode
Table 7 describes the controller states of the C300 Controller after it transitions to the
application mode. See Table 11 for a description of the faceplate indications when the
controller is operating in the application mode.
Controller
State
NODB
IDLE
OK
R301.1
11/06
invalid application image is loaded.
A
firmware upgrade
can be performed from this state if desired.
The controller receives a command to remain in the boot mode to
allow a
firmware
upgrade.
The controller detected a failure during startup.
Use the CTool utility to retrieve problem report logs from the
controller for failure diagnosis.
Table 7 C300 Controller in Application mode
The C300 Controller is configured as redundant or non-redundant
and has not retained its database from operation prior to startup.
The C300 Controller/CEE moves to the NOTLOADED state.
The C300 Controller is configured as non-redundant, or as
redundant and has assumed the primary redundancy role.
And...
Has retained a valid database from operation prior to startup,
And...
The controller is configured to do a 'Cold Start' (RRRCEESTATE
parameter).
The C300 Controller/CEE moves to the CEEIDLE state
The C300 Controller is configured as non-redundant, or as
redundant and has assumed the primary redundancy role,
And...
Has retained a valid database from previous operations prior to
startup
Experion C300 Controller User's Guide
Honeywell
C300 Controller start up
C300 Controller states in application mode
Description
161