Convert a non-redundant C300 Controller to a redundant
controller
You can convert a single non-redundant C300 Controller to a redundant controller simply
by configuring the controller as redundant. The controller icon which represents the
secondary controller is then added to the Project tab.
Prerequisites
Control Builder is running
•
Tree windows are open
•
Ensure that a C300 Controller is properly installed in the same control cabinet as the
•
C300 Controller designated to become the redundant partner. Note do not connect
the Redundancy cable between the two controllers until instructed to do so.
Considerations
This procedure can be performed on-process. All illustrations used in the procedure are
for example purposes only.
To convert a non-redundant C300 Controller to a Redundant controller
Step
1
In the Project window, right-click on the
C300_NonRED Controller block icon.
2
Click Module Properties...
R301.1
11/06
Convert a non-redundant C300 Controller to a redundant controller
To convert a non-redundant C300 Controller to a Redundant controller
Action
Experion C300 Controller User's Guide
Honeywell
Result
Calls up shortcut menu.
Calls up the C300 Block configuration
form.
49