To Assign Control Modules And Ioms To A Cee - Honeywell Experion C300 User Manual

Hide thumbs Also See for Experion C300:
Table of Contents

Advertisement

Prerequisites
Control Builder is running
Tree windows are open
Considerations
All illustrations used in the procedure are for example purposes only.
For additional information on CM assignment, see the Control Building Guide; or for
SCM assignment, the Sequential Control User's Guide.
ATTENTION

To assign Control Modules and IOMs to a CEE

Step
1
Click Edit->Execution Environment
Assignment. Or, click
button in the toolbar.
R301.1
11/06
Assign Control Modules and IOMs to a CEEC300 block
Before Control Builder allows you to associate an IOM to an
IOCHANNEL block, it checks to make sure that the CM and IOM are
assigned to the same CEE
All edit windows (such as CM charts) must be closed before
proceeding with this procedure or a lock contention may occur. To
resolve these types of lock contentions, close the open CM chart and
attempt to open the CM chart again.
Action
assignment
Experion C300 Controller User's Guide
Honeywell
To assign Control Modules and IOMs to a CEE
Result
Calls up Execution Environment
Assignment dialog box. (There is no set
default state for the dialog, so it may
come up with different active fields than
shown below.)
61