C300 Controller installation
To install a partner secondary C300 Controller
Both the primary and partner secondary controllers must be connected to the same
•
pair of FTE Control Firewall (CF9) assemblies.
To install a partner secondary C300 Controller
Step
1
If the primary C300 FB already exists in Control Builder and it is configured
as a redundant controller, make sure the auto-sync parameter is set to
"Disabled."
2
Refer to appropriate site location drawings for the specified installation
location, controller Device Index (FTE address) and wiring diagrams.
3
Select the mounting location on carrier and align mounting holes in IOTA with
screw hole locations on the carrier.
4
Be sure component side of IOTA is facing up. Secure IOTA to carrier using
screws, washers and spacers provided. Insert spacers and washers between
bottom of IOTA and top of carrier.
5
Connect FTE-A and FTE-B Ethernet link cables to the RJ-45 connectors on
C300 IOTA board.
•
The Yellow Cat5 cable connects to the "FTEA" connector on the IOTA.
•
The Green Cat5 cable connects to the "FTEB" connector on the IOTA.