Controller Faceplate
Status
Blinking
Green
LED
FTE
Blinking
Green
LEDs
Display
NODB
CB icon
Yellow

Redundant Primary C300 Controller with Memory Retention

Controller Faceplate
Status
Blinking
Red
LED
FTE
Off
LEDs
Display
BP for 2
min.
COMM
for 1 min.
TS for 3
min. then
IDLE
CB icon
Red
Status
Blinking
Orange
LED
FTE
Blinking
Green
LEDs
Display
BKUP
CB icon
Grey
R301.1
11/06
Communication and system time startup fault scenarios
Redundant Primary C300 Controller with Memory Retention
Problem
None. Normal operation for
redundant primary controller
with no battery backup
following a power cycle.
Problem
No communication on FTE
network.
Communication on FTE
network.
• No communication via CDA
• Unable to establish
connection to system time
source
Controller transitions to
secondary redundancy role
assuming its partner has CDA
available.
Experion C300 Controller User's Guide
Honeywell
C300 Block
Station Alarm
Time Source
SNTP
C300 Not
Synchronized
C300 Block
Station Alarm
Time Source
None
C300 OFFNET
None
CDA Comm Lost
Connection
Resolve
None.
Resolve
Note 1
Note 2