The controller's operating state the display shows in a rotating display the FTE
Device Index, CEE state, and soft failures (such as redundancy, communications, or
diagnostic faults).
The controller's redundancy role and synchronization status.
Fault codes when the controller ceases normal operation due to a major fault.
Table 9 includes a listing and descriptions of the various indications of the C300
Controller display.

Table 9 C300 Controller faceplate display indications

Faceplate
Display
(####)
Communication Failure – No effect on controller state,
See Note 1
shown on Control Builder forms and Station displays
Tnnn
POST test number – Transient state, No CDA.
-BP-
Controller in BootP mode waiting for IP address -
Transient state, No CDA.
-TS-
Controller is attempting connection to time server, or time
server is not available – Transient state, No CDA.
COMM
Controller not able to communicate with other nodes.
See Note 2
TEST
Factory Test mode – Non product state, No CDA.
FAIL
Failure in Module – No CDA
See Note 3
ALIV
Boot mode with no application image – No CDA
RDY
Boot mode with application image – No CDA
LOAD
Firmware load in progress – No CDA
PROG
Firmware flash in progress – No CDA
NODB
Application mode with no database – CDA present
NOEE
Application node with no CEE, but C300 FB present with
CDA. This is a transient state during loading C300 FB or
when deleting CEE FB/C300 FB
R301.1
11/06
Indicates...
Experion C300 Controller User's Guide
Honeywell
C300 faceplate indicators/displays
Faceplate display information
C300 Module
(PCMSTATE)
OFFNET
N/A
BOOTING
BOOTING
OFFNET
TESTING
FAILED
ALIVE
PIREADY
LOADING
LOADING
NOTLOADED
NOEE
State
165