The controller's operating state the display shows in a rotating display the FTE
•
Device Index, CEE state, and soft failures (such as redundancy, communications, or
diagnostic faults).
The controller's redundancy role and synchronization status.
•
Fault codes when the controller ceases normal operation due to a major fault.
•
Table 9 includes a listing and descriptions of the various indications of the C300
Controller display.
Table 9 C300 Controller faceplate display indications
Faceplate
Display
(####)
Communication Failure – No effect on controller state,
See Note 1
shown on Control Builder forms and Station displays
Tnnn
POST test number – Transient state, No CDA.
-BP-
Controller in BootP mode waiting for IP address -
Transient state, No CDA.
-TS-
Controller is attempting connection to time server, or time
server is not available – Transient state, No CDA.
COMM
Controller not able to communicate with other nodes.
See Note 2
TEST
Factory Test mode – Non product state, No CDA.
FAIL
Failure in Module – No CDA
See Note 3
ALIV
Boot mode with no application image – No CDA
RDY
Boot mode with application image – No CDA
LOAD
Firmware load in progress – No CDA
PROG
Firmware flash in progress – No CDA
NODB
Application mode with no database – CDA present
NOEE
Application node with no CEE, but C300 FB present with
CDA. This is a transient state during loading C300 FB or
when deleting CEE FB/C300 FB
R301.1
11/06
Indicates...
Experion C300 Controller User's Guide
Honeywell
C300 faceplate indicators/displays
Faceplate display information
C300 Module
(PCMSTATE)
OFFNET
N/A
BOOTING
BOOTING
OFFNET
TESTING
FAILED
ALIVE
PIREADY
LOADING
LOADING
NOTLOADED
NOEE
State