Commanding Become Primary
Step
1
In the Monitoring tab, double-click the secondary C300 icon to call up its
Parameters configuration form.
2
Click the Redundancy tab to display it.
3
Click the Become Primary button.
4
Click the Yes button to confirm the action and issue the Become Primary
command.
5
Confirm that the Secondary C300 Controller assumes the Primary role
6
Click the OK button to close the Parameters form.
7
This completes the procedure.
Initiating Switchover command
You can use the following procedure to initiate a switchover command manually to a
redundant C300 Controller pair.
Prerequisites
You can view active redundant C300 Controller pair on the Monitoring tab in
•
Control Builder.
The primary and secondary C300 Controllers are synchronized.
•
Commanding a switchover
Step
1
In the Monitoring tab, double-click the primary C300 icon to call up its
Parameters configuration form.
2
Click the Redundancy tab to display it.
3
Click the Initiate Switchover button.
4
Click the Yes button to confirm the action and issue the switchover
command.
5
Confirm that the Secondary C300 Controller assumes the Primary role. The
old primary controller should boot up in the backup role.
R301.1
11/06
Experion C300 Controller User's Guide
Honeywell
Initiating Switchover command
Commanding Become Primary
Action
Action
179