Query Types Available; Modbus Rtu Command Types - Honeywell TPPL Modbus TCP Installation And Setup Manual

Table of Contents

Advertisement

4.6.2

Query Types Available

Poll No
02
39
40
41
42
43
44
102
103
104
Query Poll Example: 'Query Type: Read Alarm 1 level':
Block Active
Register
(40n01)
1
Value
If Block Active is set to 1, the Controller processes the request. If Block Active is set to 0 the Controller will not process the
request or has already processed the request.
The sole option for 'Channel Type' is 105 – Input Channel.

4.7 Modbus RTU Command Types

Note: Due to a system limitation, TPPL will give an error message 'Command not permitted' during Administrator or
Service log on, but not when accessed by an Operator or User.
MAN0995_Iss 1_01/16
Pt. No. 3011M5027_1
M
ODBUS
Description
Read System Label
Read Alarm 1 level
Read Alarm 2 level
Read Alarm 3 level
Read STEL level
Read LTEL level
Read Rate level
Read Gas Name
Read Channel Tag Name
Read Gas Unit
Table 10.
Channel Type
Channel ID
(40n02)
(40n03)
105
2
Table 11.
Command Type
23
Alarm Acknowledge
24
Alarm Reset
25
Set Inhibit
26
Clear inhibit
Table 12.
C
ONFIGURATION
Response Format
Unicode String – 35 (Unicode chars) + 1(null)
Float (4 Bytes – 32 bit floating point)
Float (4 Bytes – 32 bit floating point)
Float (4 Bytes – 32 bit floating point)
Float (4 Bytes – 32 bit floating point)
Float (4 Bytes – 32 bit floating point)
Float (4 Bytes – 32 bit floating point)
Unicode String – 35 (Unicode chars) + 1(null)
Unicode String – 35 (Unicode chars) + 1(null)
Unicode String – 35 (Unicode chars) + 1(null)
Query Type Descriptions
Query Type
Result (40n05)
(40n04)
(Updated upon
39
request execution)
Query Poll Example
Description
Command Types
14
Result String
(40n06 to 40n36)
(Updated upon
request execution)
Touchpoint Plus
Modbus Installation Guide